Symptoms
- The axis cannot move to the limit position, and the system pops up a limit alarm.
- No alarm is triggered even when the machine runs to the extreme position.
- The equipment stops suddenly during operation randomly, showing intermittent limit signal abnormality.
- After triggering the limit, the axis cannot be released and returned normally.
Possible Causes
- The limit switch is impacted, displaced or loose after long-term operation.
- Dust, cutting slag and oil stain cover the switch contact, resulting in poor contact.
- The internal spring or reed of the switch is fatigued and fails to reset.
- Signal cable is worn, broken or the connector is loose and oxidized.
- The PLC input terminal or control board signal channel is damaged.
- The switch wiring definition is wrong, normally open and normally closed signal are mixed.
Solutions
- Power off the machine first, check the installation position and fastening status of the limit switch, and re-fix and calibrate if it is offset.
- Clean the surface of the switch and contact points with clean compressed air, remove slag, dust and oil dirt, and avoid using liquid cleaning agent directly.
- Manually trigger the switch repeatedly to test the reset performance; replace the switch if it cannot bounce back normally.
- Inspect the signal wire along the drag chain, repair broken wires and tighten the aviation plug; polish the oxidized terminals.
- Use the system IO monitoring interface to check whether the signal changes synchronously when triggering the switch, judge whether the switch or the control board is faulty.
- Confirm the normally open / normally closed setting parameters on the control system, adjust to match the actual wiring of the switch.
Notes
- Before inspection and maintenance, cut off the main power supply of the equipment to prevent accidental movement of the machine tool.
- Do not adjust the limit position arbitrarily. Too large limit range will cause collision risk of the machine.
- After replacement or debugging, test the positive and negative limit of each axis one by one to confirm that the alarm and release functions are normal.